HVAC Duct Sizing Chart

Size round and rectangular ducts from 4 to 24 inches using ASHRAE friction math and ACCA Manual D velocity caps.

Quick presets:
≈ 3 ton @ 400 CFM/ton · 566.3 L/s
in. w.g. / 100 ft
Recommended Round Duct 16 in 406 mm · Exact min: 15.64 in Velocity-limited (Manual D cap)
Air Velocity 859 FPM 4.37 m/s · Cap: 900 FPM (rec 700) Within Manual D max limit
Actual Friction Loss 0.064 in. w.g./100 ft (0.53 Pa/m) · Target ≤ 0.08 VP: 0.0460 in. w.g.
Rectangular Equivalent 22 × 10 in De 15.91 in · 785 FPM · AR 2.2:1 Huebscher aspect ratio OK (≤ 4:1)

Adjacent Round Sizes at 1,200 CFM

Visual scale & why stepping down hurts
14 in round Too tight

1123 FPM · 0.124 in. w.g./100 ft

Exceeds 900 FPM · Exceeds 0.08

16 in round Best match

859 FPM · 0.064 in. w.g./100 ft

Velocity OK · Friction OK

18 in round Oversized

679 FPM · 0.036 in. w.g./100 ft

Velocity OK · Friction OK

Rectangular Trunk Options

Matched to your airflow & friction target
Depth Rect Size Equiv Ø Velocity Aspect
8" 28 × 8 in 15.62" 771 FPM 3.5:1
10" 22 × 10 in 15.91" 785 FPM 2.2:1
12" 18 × 12 in 15.98" 800 FPM 1.5:1

Complete 4"–24" HVAC Duct Sizing Chart

Showing Galvanized steel · Supply trunk · 0.08 in. w.g./100 ft (max 900 FPM). Click any row to load its max CFM.

Round Ø Max Airflow Velocity Friction Loss Limited By 8" Deep Rect 10" Deep Rect 12" Deep Rect
4" (102 mm) 32 CFM (15 L/s) 367 FPM 0.077 Friction 4×8" 4×10" 4×12"
5" (127 mm) 59 CFM (28 L/s) 433 FPM 0.078 Friction 4×8" 4×10" 4×12"
6" (152 mm) 97 CFM (46 L/s) 494 FPM 0.079 Friction 4×8" 4×10" 4×12"
7" (178 mm) 148 CFM (70 L/s) 554 FPM 0.080 Friction 6×8" 6×10" 4×12"
8" (203 mm) 212 CFM (100 L/s) 607 FPM 0.080 Friction 8×8" 6×10" 6×12"
9" (229 mm) 290 CFM (137 L/s) 656 FPM 0.080 Friction 10×8" 8×10" 6×12"
10" (254 mm) 385 CFM (182 L/s) 706 FPM 0.080 Friction 12×8" 10×10" 8×12"
12" (305 mm) 627 CFM (296 L/s) 798 FPM 0.080 Friction 16×8" 14×10" 12×12"
14" (356 mm) 946 CFM (446 L/s) 885 FPM 0.080 Friction 22×8" 18×10" 14×12"
16" (406 mm) 1,256 CFM (593 L/s) 900 FPM 0.070 Velocity cap 30×8" 24×10" 20×12"
18" (457 mm) 1,590 CFM (750 L/s) 900 FPM 0.061 Velocity cap 40×8" 30×10" 24×12"
20" (508 mm) 1,963 CFM (926 L/s) 900 FPM 0.053 Velocity cap 52×8" 38×10" 30×12"
22" (559 mm) 2,375 CFM (1121 L/s) 900 FPM 0.048 Velocity cap 64×8" 48×10" 38×12"
24" (610 mm) 2,827 CFM (1334 L/s) 900 FPM 0.043 Velocity cap 80×8" 58×10" 46×12"

Who it’s for: HVAC installers, air-balancing techs, energy auditors, and homeowners sizing supply trunks, room branches, or return runs before cutting sheet metal or ordering flex duct.

How it works

  1. Enter your airflow in CFM (or click a tonnage or room preset at the top of the tool).
  2. Pick the duct role—supply trunk, supply branch, return trunk, or return branch—and choose galvanized steel, stretched flex duct, or fiberglass duct board.
  3. Set your target friction rate (0.08 in. w.g./100 ft is typical for residential jobs) and your joist-bay height limit for rectangular options.
  4. Read the recommended round diameter, air velocity, and rectangular match above, or click any row in the 4–24 inch sizing chart to load its capacity.

How this HVAC duct sizing chart calculates duct sizes

Most printable duct sizing charts lock you into one scenario: clean galvanized metal at 0.10 in. w.g. per 100 ft. That works for quick rough-ins, yet misses why real systems howl at grilles or starve far rooms. Here, every number in the table runs live from two engineering checks side by side: straight-duct friction loss and maximum air velocity.

Friction loss uses the Darcy-Weisbach equation paired with the Colebrook-White friction factor for standard air (70 °F, 0.075 lb/ft³). Smooth galvanized sheet metal has an absolute roughness of 0.0003 ft (0.09 mm), whereas fully stretched flexible duct and fiberglass duct board use 0.003 ft (0.9 mm). Rectangular sizes use Huebscher's equivalent diameter formula so a flat trunk fits between joists while matching the round duct's friction rate.

Take a 3-ton residential supply trunk moving 1,200 CFM at 0.08 in. w.g./100 ft in galvanized steel with a 10-inch joist depth: this tool recommends a 16 in round duct (859 FPM, 0.064 in. w.g./100 ft) or a 22 × 10 in rectangular trunk. Drop the available joist depth to 8 inches for that same 1,200 CFM supply trunk, and the rectangular width grows to 28 × 8 in. On a smaller bedroom branch carrying 150 CFM in galvanized steel, 0.08 in. w.g./100 ft selects an 8 in round duct (430 FPM), while raising the target friction rate to 0.10 in. w.g./100 ft shrinks that branch to 7 in (561 FPM).

Why velocity caps and duct material change the chart

Even when friction math permits a smaller pipe, air rushing past registers and sharp transitions gets noisy fast. Following ANSI/ACCA Manual D Table 3-1 guidelines, rigid metal supply trunks cap at 900 FPM maximum (700 FPM recommended), while return trunks cap at 700 FPM maximum (600 FPM recommended). Flexible duct caps at 700 FPM on both supply and return runs because its wire helix adds turbulence and pressure drop.

Those velocity rules flip sizing choices on larger trunks and whenever you change materials. At 0.08 in. w.g./100 ft in galvanized steel, a 900 CFM supply trunk is still friction-limited at 14 in, whereas a 1,100 CFM supply trunk becomes velocity-limited at 16 in. Switching that 1,200 CFM supply trunk from galvanized steel to flexible duct pushes the recommendation up from 16 in to 18 in (679 FPM) because flex duct hits the 700 FPM ceiling. Switching the 1,200 CFM galvanized run from a supply trunk to a return trunk also shifts the size from 16 in to 18 in round (and from 22 × 10 in to 26 × 10 in rectangular). Even at 600 CFM (1.5 tons) and 0.08 in. w.g./100 ft, changing a supply trunk from galvanized steel to flexible duct bumps the diameter from 12 in to 14 in.

Data sources, assumptions, and field limits

Friction equations and roughness factors follow Chapter 21 (Duct Design) of the ASHRAE Handbook—Fundamentals. Velocity thresholds follow ANSI/ACCA Manual D residential design tables, and rectangular equivalents follow SMACNA and Huebscher sizing practice. The active sizing chart covers standard round sizes from 4 to 24 inches, while the calculator accepts flows up to 20,000 CFM.

Three field conditions sit outside any straight-duct chart. First, flexible duct numbers assume the inner core is pulled completely taut and supported properly; a slack or 15% compressed flex run can more than double friction loss. Second, the friction rate here covers straight pipe only—always add fitting equivalent lengths (elbows, wyes, boots, and dampers) against your air handler's available static pressure. Third, calculations assume sea-level dry air near 70 °F; high-altitude installations (above 2,000 ft) move lower-density air and need higher CFM for the same sensible heat transfer.

FAQ

What duct size do I need for a 3-ton AC unit (1,200 CFM)?

At the standard 400 CFM per ton rule of thumb, a 3-ton system moves 1,200 CFM. In galvanized steel at 0.08 in. w.g./100 ft, the supply trunk needs a 16 in round duct (859 FPM) or a 22 × 10 in rectangular trunk, while the return trunk steps up to an 18 in round duct (679 FPM) or 26 × 10 in rectangular.

What friction rate should I pick on an HVAC duct sizing chart?

Most residential jobs land between 0.06 and 0.10 in. w.g. per 100 ft, with 0.08 serving as a common baseline. Lower friction rates such as 0.05 or 0.06 suit long duct runs or low-static equipment, whereas 0.10 fits compact layouts with plenty of blower static pressure to spare.

Why does flexible duct need a larger diameter than sheet metal?

Even when pulled tight, spiral-wire flex duct has roughly ten times the internal surface roughness of clean galvanized steel (0.003 ft vs. 0.0003 ft). Its Manual D maximum velocity is also capped lower at 700 FPM instead of 900 FPM, so flex runs regularly jump one standard size up—such as 14 in flex instead of 12 in steel at 600 CFM.

How do I convert a round duct size to a rectangular duct?

Match equivalent friction diameter rather than raw cross-sectional area, because rectangular corners create extra drag. Select your maximum joist-bay height (8, 10, or 12 inches) in the calculator, and it solves Huebscher's equivalent diameter formula while flagging aspect ratios wider than 4:1.

Why is a return duct larger than a supply duct at the same CFM?

Return systems sit on the suction side of the blower and usually rely on shorter paths directly back to a central grille, making blower rumble and whistle easy to hear. Manual D caps return trunks at 700 FPM (600 FPM recommended) compared with 900 FPM max for rigid supply trunks, which forces a wider duct at the same airflow.

Sources