Adjacent Round Sizes at 1,200 CFM
Visual scale & why stepping down hurtsRectangular Trunk Options
Matched to your airflow & friction target| Depth | Rect Size | Equiv Ø | Velocity | Aspect |
|---|---|---|---|---|
| 8" | 28 × 8 in | 15.62" | 771 FPM | 3.5:1 |
| 10" | 22 × 10 in | 15.91" | 785 FPM | 2.2:1 |
| 12" | 18 × 12 in | 15.98" | 800 FPM | 1.5:1 |
Complete 4"–24" HVAC Duct Sizing Chart
Showing Galvanized steel · Supply trunk · 0.08 in. w.g./100 ft (max 900 FPM). Click any row to load its max CFM.
| Round Ø | Max Airflow | Velocity | Friction Loss | Limited By | 8" Deep Rect | 10" Deep Rect | 12" Deep Rect |
|---|---|---|---|---|---|---|---|
| 4" (102 mm) | 32 CFM (15 L/s) | 367 FPM | 0.077 | Friction | 4×8" | 4×10" | 4×12" |
| 5" (127 mm) | 59 CFM (28 L/s) | 433 FPM | 0.078 | Friction | 4×8" | 4×10" | 4×12" |
| 6" (152 mm) | 97 CFM (46 L/s) | 494 FPM | 0.079 | Friction | 4×8" | 4×10" | 4×12" |
| 7" (178 mm) | 148 CFM (70 L/s) | 554 FPM | 0.080 | Friction | 6×8" | 6×10" | 4×12" |
| 8" (203 mm) | 212 CFM (100 L/s) | 607 FPM | 0.080 | Friction | 8×8" | 6×10" | 6×12" |
| 9" (229 mm) | 290 CFM (137 L/s) | 656 FPM | 0.080 | Friction | 10×8" | 8×10" | 6×12" |
| 10" (254 mm) | 385 CFM (182 L/s) | 706 FPM | 0.080 | Friction | 12×8" | 10×10" | 8×12" |
| 12" (305 mm) | 627 CFM (296 L/s) | 798 FPM | 0.080 | Friction | 16×8" | 14×10" | 12×12" |
| 14" (356 mm) | 946 CFM (446 L/s) | 885 FPM | 0.080 | Friction | 22×8" | 18×10" | 14×12" |
| 16" (406 mm) | 1,256 CFM (593 L/s) | 900 FPM | 0.070 | Velocity cap | 30×8" | 24×10" | 20×12" |
| 18" (457 mm) | 1,590 CFM (750 L/s) | 900 FPM | 0.061 | Velocity cap | 40×8" | 30×10" | 24×12" |
| 20" (508 mm) | 1,963 CFM (926 L/s) | 900 FPM | 0.053 | Velocity cap | 52×8" | 38×10" | 30×12" |
| 22" (559 mm) | 2,375 CFM (1121 L/s) | 900 FPM | 0.048 | Velocity cap | 64×8" | 48×10" | 38×12" |
| 24" (610 mm) | 2,827 CFM (1334 L/s) | 900 FPM | 0.043 | Velocity cap | 80×8" | 58×10" | 46×12" |
| Round Ø | Quiet (0.05 in. w.g.) | Standard (0.08 in. w.g.) | Compact (0.10 in. w.g.) | Vel @ 0.08 | 10" Rect Equiv |
|---|---|---|---|---|---|
| 4" (102 mm) | 25 CFM | 32 CFM | 37 CFM | 367 FPM | 4×10" |
| 5" (127 mm) | 45 CFM | 59 CFM | 67 CFM | 433 FPM | 4×10" |
| 6" (152 mm) | 75 CFM | 97 CFM | 110 CFM | 494 FPM | 4×10" |
| 7" (178 mm) | 114 CFM | 148 CFM | 167 CFM | 554 FPM | 6×10" |
| 8" (203 mm) | 163 CFM | 212 CFM | 239 CFM | 607 FPM | 6×10" |
| 9" (229 mm) | 224 CFM | 290 CFM | 328 CFM | 656 FPM | 8×10" |
| 10" (254 mm) | 297 CFM | 385 CFM | 435 CFM | 706 FPM | 10×10" |
| 12" (305 mm) | 485 CFM | 627 CFM | 706 CFM | 798 FPM | 14×10" |
| 14" (356 mm) | 732 CFM | 946 CFM | 962 CFM | 885 FPM | 18×10" |
| 16" (406 mm) | 1,046 CFM | 1,256 CFM | 1,256 CFM | 900 FPM | 24×10" |
| 18" (457 mm) | 1,431 CFM | 1,590 CFM | 1,590 CFM | 900 FPM | 30×10" |
| 20" (508 mm) | 1,894 CFM | 1,963 CFM | 1,963 CFM | 900 FPM | 38×10" |
| 22" (559 mm) | 2,375 CFM | 2,375 CFM | 2,375 CFM | 900 FPM | 48×10" |
| 24" (610 mm) | 2,827 CFM | 2,827 CFM | 2,827 CFM | 900 FPM | 58×10" |
| Cooling Size | Airflow (@ 400 CFM/ton) | Supply Trunk Ø | Supply Rect (10" H) | Return Trunk Ø | Return Rect (10" H) |
|---|---|---|---|---|---|
| 1.5 ton | 600 CFM (283 L/s) | 12" (764 FPM) | 12 × 10 in | 14" (561 FPM) | 14 × 10 in |
| 2 ton | 800 CFM (378 L/s) | 14" (748 FPM) | 16 × 10 in | 16" (573 FPM) | 18 × 10 in |
| 2.5 ton | 1,000 CFM (472 L/s) | 16" (716 FPM) | 18 × 10 in | 18" (566 FPM) | 22 × 10 in |
| 3 ton | 1,200 CFM (566 L/s) | 16" (859 FPM) | 22 × 10 in | 18" (679 FPM) | 26 × 10 in |
| 3.5 ton | 1,400 CFM (661 L/s) | 18" (792 FPM) | 24 × 10 in | 20" (642 FPM) | 30 × 10 in |
| 4 ton | 1,600 CFM (755 L/s) | 20" (733 FPM) | 26 × 10 in | 22" (606 FPM) | 34 × 10 in |
| 5 ton | 2,000 CFM (944 L/s) | 22" (758 FPM) | 32 × 10 in | 24" (637 FPM) | 42 × 10 in |
Who it’s for: HVAC installers, air-balancing techs, energy auditors, and homeowners sizing supply trunks, room branches, or return runs before cutting sheet metal or ordering flex duct.
How it works
- Enter your airflow in CFM (or click a tonnage or room preset at the top of the tool).
- Pick the duct role—supply trunk, supply branch, return trunk, or return branch—and choose galvanized steel, stretched flex duct, or fiberglass duct board.
- Set your target friction rate (0.08 in. w.g./100 ft is typical for residential jobs) and your joist-bay height limit for rectangular options.
- Read the recommended round diameter, air velocity, and rectangular match above, or click any row in the 4–24 inch sizing chart to load its capacity.
How this HVAC duct sizing chart calculates duct sizes
Most printable duct sizing charts lock you into one scenario: clean galvanized metal at 0.10 in. w.g. per 100 ft. That works for quick rough-ins, yet misses why real systems howl at grilles or starve far rooms. Here, every number in the table runs live from two engineering checks side by side: straight-duct friction loss and maximum air velocity.
Friction loss uses the Darcy-Weisbach equation paired with the Colebrook-White friction factor for standard air (70 °F, 0.075 lb/ft³). Smooth galvanized sheet metal has an absolute roughness of 0.0003 ft (0.09 mm), whereas fully stretched flexible duct and fiberglass duct board use 0.003 ft (0.9 mm). Rectangular sizes use Huebscher's equivalent diameter formula so a flat trunk fits between joists while matching the round duct's friction rate.
Take a 3-ton residential supply trunk moving 1,200 CFM at 0.08 in. w.g./100 ft in galvanized steel with a 10-inch joist depth: this tool recommends a 16 in round duct (859 FPM, 0.064 in. w.g./100 ft) or a 22 × 10 in rectangular trunk. Drop the available joist depth to 8 inches for that same 1,200 CFM supply trunk, and the rectangular width grows to 28 × 8 in. On a smaller bedroom branch carrying 150 CFM in galvanized steel, 0.08 in. w.g./100 ft selects an 8 in round duct (430 FPM), while raising the target friction rate to 0.10 in. w.g./100 ft shrinks that branch to 7 in (561 FPM).
Why velocity caps and duct material change the chart
Even when friction math permits a smaller pipe, air rushing past registers and sharp transitions gets noisy fast. Following ANSI/ACCA Manual D Table 3-1 guidelines, rigid metal supply trunks cap at 900 FPM maximum (700 FPM recommended), while return trunks cap at 700 FPM maximum (600 FPM recommended). Flexible duct caps at 700 FPM on both supply and return runs because its wire helix adds turbulence and pressure drop.
Those velocity rules flip sizing choices on larger trunks and whenever you change materials. At 0.08 in. w.g./100 ft in galvanized steel, a 900 CFM supply trunk is still friction-limited at 14 in, whereas a 1,100 CFM supply trunk becomes velocity-limited at 16 in. Switching that 1,200 CFM supply trunk from galvanized steel to flexible duct pushes the recommendation up from 16 in to 18 in (679 FPM) because flex duct hits the 700 FPM ceiling. Switching the 1,200 CFM galvanized run from a supply trunk to a return trunk also shifts the size from 16 in to 18 in round (and from 22 × 10 in to 26 × 10 in rectangular). Even at 600 CFM (1.5 tons) and 0.08 in. w.g./100 ft, changing a supply trunk from galvanized steel to flexible duct bumps the diameter from 12 in to 14 in.
Data sources, assumptions, and field limits
Friction equations and roughness factors follow Chapter 21 (Duct Design) of the ASHRAE Handbook—Fundamentals. Velocity thresholds follow ANSI/ACCA Manual D residential design tables, and rectangular equivalents follow SMACNA and Huebscher sizing practice. The active sizing chart covers standard round sizes from 4 to 24 inches, while the calculator accepts flows up to 20,000 CFM.
Three field conditions sit outside any straight-duct chart. First, flexible duct numbers assume the inner core is pulled completely taut and supported properly; a slack or 15% compressed flex run can more than double friction loss. Second, the friction rate here covers straight pipe only—always add fitting equivalent lengths (elbows, wyes, boots, and dampers) against your air handler's available static pressure. Third, calculations assume sea-level dry air near 70 °F; high-altitude installations (above 2,000 ft) move lower-density air and need higher CFM for the same sensible heat transfer.
FAQ
What duct size do I need for a 3-ton AC unit (1,200 CFM)?
At the standard 400 CFM per ton rule of thumb, a 3-ton system moves 1,200 CFM. In galvanized steel at 0.08 in. w.g./100 ft, the supply trunk needs a 16 in round duct (859 FPM) or a 22 × 10 in rectangular trunk, while the return trunk steps up to an 18 in round duct (679 FPM) or 26 × 10 in rectangular.
What friction rate should I pick on an HVAC duct sizing chart?
Most residential jobs land between 0.06 and 0.10 in. w.g. per 100 ft, with 0.08 serving as a common baseline. Lower friction rates such as 0.05 or 0.06 suit long duct runs or low-static equipment, whereas 0.10 fits compact layouts with plenty of blower static pressure to spare.
Why does flexible duct need a larger diameter than sheet metal?
Even when pulled tight, spiral-wire flex duct has roughly ten times the internal surface roughness of clean galvanized steel (0.003 ft vs. 0.0003 ft). Its Manual D maximum velocity is also capped lower at 700 FPM instead of 900 FPM, so flex runs regularly jump one standard size up—such as 14 in flex instead of 12 in steel at 600 CFM.
How do I convert a round duct size to a rectangular duct?
Match equivalent friction diameter rather than raw cross-sectional area, because rectangular corners create extra drag. Select your maximum joist-bay height (8, 10, or 12 inches) in the calculator, and it solves Huebscher's equivalent diameter formula while flagging aspect ratios wider than 4:1.
Why is a return duct larger than a supply duct at the same CFM?
Return systems sit on the suction side of the blower and usually rely on shorter paths directly back to a central grille, making blower rumble and whistle easy to hear. Manual D caps return trunks at 700 FPM (600 FPM recommended) compared with 900 FPM max for rigid supply trunks, which forces a wider duct at the same airflow.